naperlou
User Rank
Blogger
Another loose connection
naperlou   8/7/2012 9:01:09 AM
NO RATINGS
Happens all the time.  There have been numerous articles on this site about such situations.  I know I have "fixed" plenty of problems where it was just a loose wire.  It is tragic that someone was killed by the circuit breaker situation.  Repeatedly doing the same thing is inviting a problem.  Thankfully, it is not usually so deadly.

TJ McDermott
User Rank
Blogger
Re: Another loose connection
TJ McDermott   8/7/2012 3:38:02 PM
NO RATINGS
Checking the torque of electrical terminations is a normal part of scheduled electrical maintenance of industrial machinery.  I don't know that I would check every low voltage connection, all of the high voltage connections (those that could likely heat up by being loose) should be.

 

ab3a
User Rank
Platinum
Re: Another loose connection
ab3a   8/17/2012 12:26:15 PM
NO RATINGS
We have used Infrared imaging since the mid 1980s at least to find and fix these problems before they get ugly.

 

It ought to be a regular part of scheduled maintenance to pull off the cover of a panel and take infrared pictures of all the screw terminals. 

monster69
User Rank
Iron
Re: Another loose connection
monster69   8/18/2012 1:01:16 PM
NO RATINGS
1 saves
In my 50th year as a volunteer fireman, I wholeheartedly agree.  Mhy story was my daughters 1st birthday party, also the 1st anniversary of our new house.  There was a pop and the the stove went dead with the roast uncooked.  I checked the breaker and it hadn't tripped.  I turned off the breaker and pulled the stove out, removed the terminal cover since it was hardwired and turned the breaker back on.  One side was open at the stove.  Turned the breaker back off and pulled the panel cover.  Lo and behold the screws on the wire were never tightened.  Properly tightened and everything back together in a half hoiur, the roast was cooked.

Bill R.
User Rank
Iron
Re: Another loose connection
Bill R.   4/19/2013 1:06:56 PM
NO RATINGS
I agree with the comment you made regarding the essential need for regularly scheduled maintenence of electrical distribution and utilization systems in facilities including infrared scans of all terminations.

To expand upon your recommendation, this work must be done when the electrical distribution system equipment (including but not limited to switchgear, switchboards, transformers, distribution panels, motor control centers, equipment or process control system cabinets or enclosures) have "dead front" (defined as intentionally grounded and not intended to conduct electricity under normal operating and energized conditions) covers have been removed as you indicated.

Removal of the dead front covers while any equipment is energized is an inherently dangerous and possibly lethal activity for the person(s) engaged in the operation.

Work is being done based on IEEE Standards which are being continuously refined, in the industry and and is addressed by OSHA to provide means to determine by calculation of the Arc-flash hazard for new and existing electrical distribution and utilizations systems in new and installations. The Arc-flash hazard classes address the different ranges energy that may exist due to the occurrance of an arc-flash at a specific location in an electrical distribution or utilization system.  Arc-flash energy above Class 4 has no equivalent PPE because anyone within normal working distances from the arc-flash source cannot be protected by apparel.  The blast pressure generated by the arc-flash having an energy greater than the upper limit specied for PPE Class 4 would probably be lethal. 

The point I want to make is that whenever energized electrical equipment is opened, a serious hazard exists.  There are four classes of Personal Protective Equipment (PPE Class 1-4) that have been defined for personnel to wear whenever they are expsed to a specific energy hazard level.  Apparel specific to meet the requirements of each class of protection is available o allow workers to be in specified distances from energized equipment.

I repectfully urge anyone who is involved with the operation, maintenance, construction or modification of electrical distribution or utilization systems and equipment to determine the hazard classes for each electrical system with which you are involved before any proceeding with any operation involving exposed electrical terminations or equipment, especially those activities involving determining whether the equipment is energized or not, and making voltage, current or other electrical state (power, power factor, power quality, etc.) masurments.

Carmine
User Rank
Iron
FLIR Camera to identify hot spots
Carmine   8/7/2012 10:00:20 AM
NO RATINGS
Years ago I worked for a company that contracted a service to image each electrical panel in the plant with a FLIR camera. This process was part of their Preventative Maintenance (PM) program and was designed to identify these types of failures before they interrupted production. FLIR camera prices have fallen over the years making this type of PM much more affordable.

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/7/2012 3:34:36 PM
NO RATINGS
So I take it, Carmine, that the program was successful at identifying faulty panels. How exactly did it work?

Carmine
User Rank
Iron
Re: FLIR Camera to identify hot spots
Carmine   8/7/2012 3:45:54 PM
At regular intervals (I think it was yearly) a PM task for Panel Imaging would be created.  The contractors would be contacted and would come and take Infrared pictures of all the Electrical panels (including panels containing control circuitry such as motor drives and PLCs). 

They would then visually analyze these pictures to locate any "hot spots"  These hot spots could be caused by a loose connection that just needed to be tightened or a failing component, etc.

Island_Al
User Rank
Gold
Re: FLIR Camera to identify hot spots
Island_Al   8/8/2012 9:24:24 AM
NO RATINGS
We used an IR camera the same way on a 3 phase 13.8kv line feeding our military facility. At every insulator on the 1/2 mile run, I had a guy take a monthly photograph. We were working next to the ocean and salt residue would build up on the insulators decreasing the resistance, causing heat, and eventually burn through. Fixing these was a nasty job and we had to post a guard at the power transfer switch. But using the camera, most of the time we would kill the power and simply clean the insulator using a pressure washer. It would seem like insulators are perfect, but a few meg ohm resistance (cable insulation/insulator) could have knocked the site off line for days. Nasty stuff that HV power is. I hate it. Explains why I love TTL so much.

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/8/2012 10:59:21 AM
NO RATINGS
Carmine, were these infrared pictures sufficient to determine the health of the electrical panels. Or, were they combined with additional inspections?

lynnbr2
User Rank
Iron
Re: FLIR Camera to identify hot spots
lynnbr2   8/8/2012 12:13:11 PM
NO RATINGS
There is now IR-friendly glass that can be added to any cabinet to create a viewport so that the internal circuitry can be imaged by the thermal camera without opening the cabinet.

This is especially handy on Motor Control Centers that employ and interlock on the door. However, because of the increased engineering req'd and subsequent addt'l BoM cost, they are not common.

A whitepaper on this topic can be found at: http://www.electrophysics.com/nl/th0708/ 

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/8/2012 1:31:39 PM
NO RATINGS
Thanks for the info, Lynnbr2. This is very helpful. What a great system. What what you suggest, it sounds expensive.

schmadel
User Rank
Iron
Re: FLIR Camera to identify hot spots
schmadel   8/9/2012 10:53:54 AM
NO RATINGS
The thermal system explained by lynnbr2 is a good approach. There are inexpensive point and click systems that use a laser beam to determine the emissivity at a particular wavelength, and then a thermal sensor to measure the emission near that wavelength. These hand held systems are sold for consumers for use in kitchens for measuring the temperature of a pot, or a roast, or a pot roast...  But when using a thermal approach one must have the circuit under significant power.

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/9/2012 11:30:28 AM
NO RATINGS
Interesting, Schmadel. So these use both laser and a thermal sensor and they're still not expensive.

schmadel
User Rank
Iron
Re: FLIR Camera to identify hot spots
schmadel   8/9/2012 12:19:39 PM
NO RATINGS
Hi Bob,

Here's a link to some optical thermometers.

http://www.allqa.com/IRcompare.htm

Some use IR lasers for the emissivity calibration, some use additional sighting lasers in the visible, and some have no lasers.

I also recal seeing our HVAC people using some with red sighting lasers to check hydronic heating systems.

These things seem to range in the $50 to $500 range.

-Don

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/9/2012 12:32:33 PM
NO RATINGS
Those prices seem reasonable, Schmadel. How about accuracy. Do they catch most of the problems -- or potential problems?

schmadel
User Rank
Iron
Re: FLIR Camera to identify hot spots
schmadel   8/13/2012 1:35:15 PM
NO RATINGS
Hi Rob,

Sorry to take so long to get back to you.

I cant' be of much help as I've never used any of these systems to discover overheated connections. The systems, like those provided by Omega, boast an accracy of about 1 degree C. This should be fine for line-of-sight instances. But for connections inside panels something like the glass covers mentioned by lynnbr2 might work.

Incidentally, the link to ElectroPhysics didn't mention anything about glass covers.

-Don

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/13/2012 5:27:52 PM
NO RATINGS
Sounds like it's limited what it might catch. 

schmadel
User Rank
Iron
Re: FLIR Camera to identify hot spots
schmadel   8/9/2012 12:20:56 PM
NO RATINGS
Sorry, I mean to type "Rob" not "Bob".

-Don

Jack Rupert, PE
User Rank
Platinum
Re: FLIR Camera to identify hot spots
Jack Rupert, PE   8/9/2012 10:21:46 AM
NO RATINGS
Great idea @lynnbr2.  Anything that makes safety reviews and maintenance easier increases the likelihood that it will be performed.  I like the idea of IR friendly glass which not only makes the checks easier, in many cases it means the checks do not require a process shutdown.

lynnbr2
User Rank
Iron
Re: FLIR Camera to identify hot spots
lynnbr2   8/9/2012 12:31:24 PM
NO RATINGS
an e-book on IR Viewports which includes basic design and application information is available at: http://www.iriss.com/Ten_things_about_Infrared-Windows_enquiry_form.php  

OLD_CURMUDGEON
User Rank
Platinum
"HOT" SPOTS
OLD_CURMUDGEON   8/8/2012 12:11:35 PM
NO RATINGS
I can vouch for several occurrences of "hot" spots in facilities wiring systems.  The supply voltage surely doesn't have to be in the kilovolt range either.  I've seen dedicated 208/240 (delta / wye) lighting panels explode.  The problem with these panels is NOT ONLY a possible loose lug on the busbars, but also excessive harmonic currents due to the inductive ballasts of large quantities of fluourescent fixtures in place.  These i²r losses can come back to haunt a good lighting load design.

Personally, I've experienced similar scary moments at home.  Since the air handler is situated in the attic crawlspace, separate from the circuit panel, the code requires a disconnect at that location.  One day I happened to be up there inspecting things, when I decided to remove the cover from the 2-circuit circuit breaker disconnect.  Aluminum cable supplied the load (heat strips for wintertime use).  One of the poles of the circuit breaker was blackened due to heat treating because of the oxidation of the aluminum conductor & resultant i²r losses.  The insulation within about 2" of the lug was evaporated.  It was a lucky thing that the electrician dressed the conductors in such a manner that they were not resting on each other, OR there would have been an "interesting" series of phone calls ....... first to the fire department to put out the roof fire, and then to the insurance company for a loss claim.  I was lucky that there was plenty of slack in the supply cable, so I replaced the mini-panel & doused the lugs & conductors with heaping gobs of NO-ALOX, anti-oxidizing compound.  Been fine ever since, and ever year I instruct the A/C service person to check the connections in that disconnect!

 

mblazer
User Rank
Silver
I2R means heat
mblazer   8/16/2012 4:19:21 PM
NO RATINGS
I had a similar problem with our test station when I was in the Air Force.  We were blowing the B phase fuse about once per day.  First 45A fuses and then 60A ones.  The Clamp-On Ammeter that we were only drawing 17A on each phase.  It turned out water had gotten into the box and corroded the contact under the fuse clip.  The fuse wasn't blowing, it was melting.  After 3 more visits from Civil Engineering, and explaining Ohms Law, they replaced the box.

Rob Spiegel
User Rank
Blogger
Re: I2R means heat
Rob Spiegel   8/16/2012 4:39:32 PM
NO RATINGS
Hey, Mblazer, you may want to write up your story and send it along for inclusion in the Sherlock Ohms blog. We need at least 350 words. Simply explain the problem you faced and show how you solved it. 

You can send it to: rob.spiegel@ubm.com

Tool_maker
User Rank
Platinum
Re: I2R means heat
Tool_maker   8/16/2012 4:42:55 PM
NO RATINGS
  I am sorry if this comes of as a smart alec, but did you slap the guy who replaced blown 45A fuses with 60A? There are reasons for the sizes of fuses in any given circuitry and to just ignore that is a recipe for big trouble.

mblazer
User Rank
Silver
Re: I2R means heat
mblazer   8/16/2012 6:30:12 PM
NO RATINGS
Yes we did (verablly at least).  Fortuantely this was just a disconnect box.  The main breaker was was located in another room with 50A breakers.

ishkabbible
User Rank
Iron
Those pesky loose wires
ishkabbible   8/16/2012 9:32:28 PM
NO RATINGS
I had a similar experience while I was maintaining a large VAX / PDP-11 installation. Every Tuesday morning we would come in and one of the PDP-11/70s would be down. I puzzled over this for weeks, left a program running overnight that just wrote the time to one of the terminals every 5 seconds, and found that it was strikingly regularly crashing at 6:30AM plus or minus a few minutes. The next Tuesday I came in early and was sitting in the computer room at 6:30 - I heard a crash from outside and the front panel lights froze. I ran outside to see the garbage truck pulling away. The dumpster was about 10 feet from the main power box feeding the building. I opened up the box and could see signs of heat on one leg of the 3 phase power. The screw lug holding the wire was loose, and when the garbage truck would drop the dumpster, there was enough vibration to cause just enough of a power glitch to crash the one computer that we had plugged into that leg. Tightened the screw and no more crashes.

William K.
User Rank
Platinum
Blowing fuses and tripping overloads
William K.   8/18/2012 8:53:28 PM
NO RATINGS
At one job, as the electrical engineer, I was asked to check into why one of the hydraulic pumps was usually "overloading". At this company it was standard procedure to use an ammeter clamped on one leg of a pump motor to set the relief valve, or adjust the pump compensator. This pump was one of two pumps arranged to assure that the big pumps always had a positive pressure at their inlets. They figured that the pump with the problem must have an excessive load, but the ammeter reading indicated less current on one phase. 

The solution was to tighten the connection terminal screws in the motor starter. One loose screw was causing much more heat to be produced in the connection, causing the thermal overload device to shut down. Raising the trip current setting had just delayed the shutoff time. So with all connections tightened, I reset the overload trip point to the recommended value. The problem was solved and my reputation was enhanced. 



Partner Zone
Latest Analysis
The National Highway Traffic Safety Administrationís recent backup camera mandate could open the door to more vehicle innovations, including better graphical displays, 360-degree camera views, and the increased use of Ethernet.
With support from National Instruments, a group of dedicated students from Connally High School in Austin, where more than 50% of the students are at risk of not graduating, have created a successful robotics team that is competing in the FIRST World Championships.
Solar Impulse 2 -- a 100% solar-powered airplane -- has been completed. It features several advanced materials, some developed specifically for next year's attempted around-the-world flight.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Lumus and eyeSight have partnered to create consumer-grade devices that offer all the prime functions of smart glasses without the bulk.
More:Blogs|News
Design News Webinar Series
3/27/2014 11:00 a.m. California / 2:00 p.m. New York / 7:00 p.m. London
2/27/2014 11:00 a.m. California / 2:00 p.m. New York / 7:00 p.m. London
12/18/2013 Available On Demand
11/20/2013 Available On Demand
Quick Poll
The Continuing Education Center offers engineers an entirely new way to get the education they need to formulate next-generation solutions.
Apr 21 - 25, Creating & Testing Your First RTOS Application Using MQX
SEMESTERS: 1  |  2  |  3  |  4  |  5


Focus on Fundamentals consists of 45-minute on-line classes that cover a host of technologies. You learn without leaving the comfort of your desk. All classes are taught by subject-matter experts and all are archived. So if you can't attend live, attend at your convenience.
Next Class: April 29 - Day 1
Sponsored by maxon precision motors
Learn More   |   Login   |   Archived Classes
Twitter Feed
Design News Twitter Feed
Like Us on Facebook

Sponsored Content

Technology Marketplace

Datasheets.com Parts Search

185 million searchable parts
(please enter a part number or hit search to begin)
Copyright © 2014 UBM Canon, A UBM company, All rights reserved. Privacy Policy | Terms of Service