naperlou
User Rank
Blogger
Another loose connection
naperlou   8/7/2012 9:01:09 AM
NO RATINGS
Happens all the time.  There have been numerous articles on this site about such situations.  I know I have "fixed" plenty of problems where it was just a loose wire.  It is tragic that someone was killed by the circuit breaker situation.  Repeatedly doing the same thing is inviting a problem.  Thankfully, it is not usually so deadly.

Carmine
User Rank
Iron
FLIR Camera to identify hot spots
Carmine   8/7/2012 10:00:20 AM
NO RATINGS
Years ago I worked for a company that contracted a service to image each electrical panel in the plant with a FLIR camera. This process was part of their Preventative Maintenance (PM) program and was designed to identify these types of failures before they interrupted production. FLIR camera prices have fallen over the years making this type of PM much more affordable.

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/7/2012 3:34:36 PM
NO RATINGS
So I take it, Carmine, that the program was successful at identifying faulty panels. How exactly did it work?

TJ McDermott
User Rank
Blogger
Re: Another loose connection
TJ McDermott   8/7/2012 3:38:02 PM
NO RATINGS
Checking the torque of electrical terminations is a normal part of scheduled electrical maintenance of industrial machinery.  I don't know that I would check every low voltage connection, all of the high voltage connections (those that could likely heat up by being loose) should be.

 

Carmine
User Rank
Iron
Re: FLIR Camera to identify hot spots
Carmine   8/7/2012 3:45:54 PM
At regular intervals (I think it was yearly) a PM task for Panel Imaging would be created.  The contractors would be contacted and would come and take Infrared pictures of all the Electrical panels (including panels containing control circuitry such as motor drives and PLCs). 

They would then visually analyze these pictures to locate any "hot spots"  These hot spots could be caused by a loose connection that just needed to be tightened or a failing component, etc.

Island_Al
User Rank
Gold
Re: FLIR Camera to identify hot spots
Island_Al   8/8/2012 9:24:24 AM
NO RATINGS
We used an IR camera the same way on a 3 phase 13.8kv line feeding our military facility. At every insulator on the 1/2 mile run, I had a guy take a monthly photograph. We were working next to the ocean and salt residue would build up on the insulators decreasing the resistance, causing heat, and eventually burn through. Fixing these was a nasty job and we had to post a guard at the power transfer switch. But using the camera, most of the time we would kill the power and simply clean the insulator using a pressure washer. It would seem like insulators are perfect, but a few meg ohm resistance (cable insulation/insulator) could have knocked the site off line for days. Nasty stuff that HV power is. I hate it. Explains why I love TTL so much.

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/8/2012 10:59:21 AM
NO RATINGS
Carmine, were these infrared pictures sufficient to determine the health of the electrical panels. Or, were they combined with additional inspections?

OLD_CURMUDGEON
User Rank
Platinum
"HOT" SPOTS
OLD_CURMUDGEON   8/8/2012 12:11:35 PM
NO RATINGS
I can vouch for several occurrences of "hot" spots in facilities wiring systems.  The supply voltage surely doesn't have to be in the kilovolt range either.  I've seen dedicated 208/240 (delta / wye) lighting panels explode.  The problem with these panels is NOT ONLY a possible loose lug on the busbars, but also excessive harmonic currents due to the inductive ballasts of large quantities of fluourescent fixtures in place.  These i²r losses can come back to haunt a good lighting load design.

Personally, I've experienced similar scary moments at home.  Since the air handler is situated in the attic crawlspace, separate from the circuit panel, the code requires a disconnect at that location.  One day I happened to be up there inspecting things, when I decided to remove the cover from the 2-circuit circuit breaker disconnect.  Aluminum cable supplied the load (heat strips for wintertime use).  One of the poles of the circuit breaker was blackened due to heat treating because of the oxidation of the aluminum conductor & resultant i²r losses.  The insulation within about 2" of the lug was evaporated.  It was a lucky thing that the electrician dressed the conductors in such a manner that they were not resting on each other, OR there would have been an "interesting" series of phone calls ....... first to the fire department to put out the roof fire, and then to the insurance company for a loss claim.  I was lucky that there was plenty of slack in the supply cable, so I replaced the mini-panel & doused the lugs & conductors with heaping gobs of NO-ALOX, anti-oxidizing compound.  Been fine ever since, and ever year I instruct the A/C service person to check the connections in that disconnect!

 

lynnbr2
User Rank
Iron
Re: FLIR Camera to identify hot spots
lynnbr2   8/8/2012 12:13:11 PM
NO RATINGS
There is now IR-friendly glass that can be added to any cabinet to create a viewport so that the internal circuitry can be imaged by the thermal camera without opening the cabinet.

This is especially handy on Motor Control Centers that employ and interlock on the door. However, because of the increased engineering req'd and subsequent addt'l BoM cost, they are not common.

A whitepaper on this topic can be found at: http://www.electrophysics.com/nl/th0708/ 

Rob Spiegel
User Rank
Blogger
Re: FLIR Camera to identify hot spots
Rob Spiegel   8/8/2012 1:31:39 PM
NO RATINGS
Thanks for the info, Lynnbr2. This is very helpful. What a great system. What what you suggest, it sounds expensive.

Page 1/3  >  >>


Partner Zone
Latest Analysis
Thanksgiving is a time for family. A time for togetherness. A time for… tech?
The promise of the Internet of Things (IoT) is that devices, gadgets, and appliances we use every day will be able to communicate with one another. This potential is not limited to household items or smartphones, but also things we find in our yard and garden, as evidenced by a recent challenge from the element14 design community.
Researchers have developed a new flexible fabric that integrates both movement and sensors, introducing new potential for technology-embedded clothing and soft robots.
Made by Monkeys highlights products that somehow slipped by the QC cops.
If you didn't realize that PowerPoint presentations are inherently hilarious, you have to see Don McMillan take one apart. McMillan -- aka the Technically Funny Comic -- worked for 10 years as an engineer before he switched to stand-up comedy.
More:Blogs|News
Design News Webinar Series
11/19/2014 11:00 a.m. California / 2:00 p.m. New York
11/6/2014 11:00 a.m. California / 2:00 p.m. New York
10/7/2014 8:00 a.m. California / 11:00 a.m. New York
12/11/2014 8:00 a.m. California / 11:00 a.m. New York
Quick Poll
The Continuing Education Center offers engineers an entirely new way to get the education they need to formulate next-generation solutions.
Dec 1 - 5, An Introduction to Embedded Software Architecture and Design
SEMESTERS: 1  |  2  |  3  |  4  |  5  |  6


Focus on Fundamentals consists of 45-minute on-line classes that cover a host of technologies. You learn without leaving the comfort of your desk. All classes are taught by subject-matter experts and all are archived. So if you can't attend live, attend at your convenience.
Last Archived Class
Sponsored by Littelfuse
Learn More   |   Login   |   Archived Classes
Twitter Feed
Design News Twitter Feed
Like Us on Facebook

Sponsored Content

Technology Marketplace

Copyright © 2014 UBM Canon, A UBM company, All rights reserved. Privacy Policy | Terms of Service