How many wires in a box?
Jon Titus   4/11/2012 11:38:36 AM
NO RATINGS
Hi, OLD_CURMUDGEON.  The electrical code specifies a certain size box given the number and gauges of wires in the box. So if you overstuff a box, your work won't pass inspection. Boxes should have their volume clearly marked and a calculation yields the volume needed for the wires.  Fine Homebuilding magazine ran an article that includes an example: http://www.finehomebuilding.com/how-to/articles/more-wires-need-bigger-boxes.aspx.

OldGeek
User Rank
Iron
Re: LAMP SOCKETS, etal....
OldGeek   4/11/2012 11:42:06 AM
NO RATINGS
Jon, I think you're dead on about the need for an update in socket design. I'm also pretty sure it won't happen any time soon just because of the enormous number of installed sockets. If a good design comes forward that could be easily fitted to existing sockets by using a screw in adapter it would have a much better chance.

Your particular problem is primarily because of the 3-way design. In the standard base, the rivets don't have to remain tight because the spring on the center contact keeps them held against the socket shell. Because the third contact of your socket is solid, the only thing holding the rivet tight is the springiness of the socket shell and that doesn't have enough "give" to be much help. If you can't find a socket with a spring third contact the addition of a screw might be your best shot, especially if you add a spring lock washer.

While a brass socket shell SOUNDS like a good idea, it has one major flaw: all modern light bulbs have an aluminum base. Brass sockets went out of favor soon after bulb bases changed to aluminum, probably because electrolytic corrosion started cementing bulbs into sockets.

Best of luck in your quest for the perfect socket :-)

 

Jon Titus
User Rank
Blogger
Re: LAMP SOCKETS, etal....
Jon Titus   4/11/2012 11:53:56 AM
Even aluminum-on-aluminum sockets can have problems, so i always put a thin coat of high-temperature silicone vacuum grease on threads before I screw in a new bulb.  I use Dow-Corning "High Vacuum Grease." The price ranges from about $20 to $32 for a 150-gram tube, but it will last for several generations.  I also use this grease on outdoor electrical and RF connectors to provide additional water resistance.

Bernie
User Rank
Iron
Poor lamp socket design
Bernie   4/11/2012 3:28:48 PM
NO RATINGS
Toward the end of the 1960's, aluminum was used for house wiring.  There were fires, initially in travel homes, but later, regular homes also experienced fires.  The cause was aluminum wires.  Aluminum has two properties that caused this problem.  First, it is a soft metal, and second, its oxide is a tough film, and an insulator.  In the case of the home wiring, vibration in mobile homes during delivery or driving, loosened the screws in the receptacle and socket contacts.  This was followed by oxidation and a reduction in the contact area because some of it was oxidized and became an insulator.  The result was heating at the contacts.

A similar problem arose with stationary homes.  Here, since the aluminum wires were softer than the brass contacts, if the wires at the contacts heated enough, the aluminum would deform because of the restriction of the contact screws.  When the contact cooled, the aluminum would contract and now there would be space where the aluminum could oxidize.

It is possible that this mechanism was the cause of the failed socket.

Tool_maker
User Rank
Platinum
new vs old
Tool_maker   4/12/2012 4:56:02 PM
NO RATINGS
I read so many posts in this publication about the failures of new elecric devices that I have to wonder if any manufacturer knows how to make reliable electrics today. I am a fan of estate sales and have a great deal of luck with refurbishing old stuff.

On the aluminum wiring, I heard years ago that it has a higher resistance than copper, so powering the exact same devices in a house with aluminum wire will cost more than if the wire is copper. Does anyone know if that is correct?

I also replace all "bulb down sockets" with pocelain. Ceiling fans for example and put a drop of WD 40 on aluminum light bulb bases. It seems to make bulbs easier to change.

Jon Titus
User Rank
Blogger
Re: new vs old
Jon Titus   4/12/2012 5:29:17 PM
Yes, aluminum has a higher resistivity than copper, but the resistance overall is so low compared to the load resistance that you lose an insignificant amount of energy in either type of wire. Instead of WD-40, try the silicone grease I recommended in an earlier blog post.  WD-40 is a water displacement agent used to help prevent corrosion.

Larry M
User Rank
Platinum
Re: LAMP SOCKETS, etal....
Larry M   4/23/2012 10:36:08 AM
NO RATINGS
Jon Titus wrote: " I also thought about running a 2-56 bolt through the brass tubing, tightening it and locking it in place. I might do that if I can't find an Eagle or Leviton replacement with a solid connection. We'll see..."

 

Jon, I've done this. I had to drill through the rivet, thinning it's walls, for the 2-56 machine screw to clear. The repair was easy and successful.

Jon Titus
User Rank
Blogger
Re: LAMP SOCKETS, etal....
Jon Titus   4/23/2012 6:54:46 PM
NO RATINGS
Good to know, Larry.  Thankfully I found a good quality socket, but I also have some 2-56 hardware handy, too.

<<  <  Page 3/3


Partner Zone
Latest Analysis
Factory floor engineers may soon be able to operate machinery and monitor equipment status simply by tapping their eyeglasses.
GE Aviation not only plans to use 3D printing to mass-produce metal parts for its LEAP jet engine, but it's also developing a separate technology for 3D-printing metal parts used in its other engines.
In this TED presentation, Wayne Cotter, a computer engineer turned standup comic, explains why engineers are natural comedians.
IBM's new SyNAPSE chip makes it possible for computers to both memorize and compute simultaneously.
The “Space Kid,” 11, will be one of the first civilians to have his design manufactured in space by NASA, thanks to the City X Project, which inspires kids to think about new 3D-printed inventions that could be useful for humans living in space.
More:Blogs|News
Design News Webinar Series
9/10/2014 11:00 a.m. California / 2:00 p.m. New York
7/23/2014 11:00 a.m. California / 2:00 p.m. New York
7/17/2014 11:00 a.m. California / 2:00 p.m. New York
6/25/2014 11:00 a.m. California / 2:00 p.m. New York
Quick Poll
The Continuing Education Center offers engineers an entirely new way to get the education they need to formulate next-generation solutions.
Sep 22 - 26, MCU Software Development – A Step-by-Step Guide (Using a Real Eval Board)
SEMESTERS: 1  |  2  |  3  |  4  |  5  |  6


Focus on Fundamentals consists of 45-minute on-line classes that cover a host of technologies. You learn without leaving the comfort of your desk. All classes are taught by subject-matter experts and all are archived. So if you can't attend live, attend at your convenience.
Next Class: September 30 - October 2
Sponsored by Altera
Learn More   |   Login   |   Archived Classes
Twitter Feed
Design News Twitter Feed
Like Us on Facebook

Sponsored Content

Technology Marketplace

Copyright © 2014 UBM Canon, A UBM company, All rights reserved. Privacy Policy | Terms of Service