naperlou
User Rank
Blogger
Shorter signal path
naperlou   8/14/2012 9:02:24 AM
NO RATINGS
I was wondering, as I was reading the article, why you did not look at shortening the signal path.  I can think of reasons, but I am wondering what the situation is in this case.

GlennA
User Rank
Gold
ground loop ?
GlennA   8/14/2012 11:07:31 AM
NO RATINGS
You mention using shielded cables.  Did you ground only one end of the cable shield ?  I have seen installations with both ends of the cable shield connected to ground, which makes ground loops a concern.

kf2qd
User Rank
Platinum
WHy not proper shielding?
kf2qd   8/14/2012 11:30:30 AM
NO RATINGS
Having built and serviced CNC plasma cutting machines, proper shielding of cables does wonders. The comercial products we used all had shielding built into the harness to keep the noise out. And the shields were always grounded at 1 end only., and in some cases where the design was older and more sensitive they actually had 2 shields, insulated from each other and each one grounded at opposite ends of the cable.

Also - effort should be made to seperate the motor and encoder cables. Often just having them shielded and a few inches apart is sufficient.

ttemple
User Rank
Platinum
Re: WHy not proper shielding?
ttemple   8/14/2012 1:34:23 PM
NO RATINGS
While it doesn't explicitly state it in the article, it appears that the encoders in question have single ended outputs.  It appears that the extenders convert the signals to differential mode, which is much more noise tolerant.  Shielding is a good idea, but with single ended signals I doubt it would have been enough if there is serious high frequency switching noise all around.

TJ McDermott
User Rank
Blogger
Re: WHy not proper shielding?
TJ McDermott   8/15/2012 12:52:19 AM
NO RATINGS
Signal cable shielding should be grounded at one end only, but shouldn't motor cable shielding be grounded at both ends?

kf2qd
User Rank
Platinum
Re: WHy not proper shielding?
kf2qd   8/15/2012 11:51:43 AM
NO RATINGS
Single ended encoders will work just fine. Plasma machines with 5V single ended encoders and proper shielding and machine grounding will work just fine. Because of the arc involved in Plasma cutting poor machine grounding can induce pulses in the various electrical circuits and cause damage. And grounding is at times a black art... Machines that run fine in one location with minimal attention to grounding practice won't function in another area without special grounding practice.

If you connect a shield at both ends it becomes a ground wire and can cause even more problems if and when there are gound currents. The purpose of a shield is to block and blead off any external electromagnetic garbage, not to act as a possible conductor. There should be a dedicated ground wire in the motor harness.

Another important thing to consider is GROUND LOOPS. If you have multiple ground paths on a machine you have the potential for different currents to flow in the various ground wires/paths. Then your grounds are no longer at the same reference and wierd and wonderful things can happen like solid state components turning on and off seemingly at random.

TJ McDermott
User Rank
Blogger
Re: WHy not proper shielding?
TJ McDermott   8/15/2012 11:59:36 AM
NO RATINGS
I should have been more specific - I was talking about the power cable for a motor.  Quoting from one drive manufacturer's installation manual:

The Shield terminal provides a grounding point for the motor cable
shield. It must be connected to an earth ground by a separate continuous lead.
The motor cable shield should be connected to this terminal on the drive (drive
end) and the motor frame (motor end). Use a shield terminating or EMI clamp
to connect shield to this terminal.

Motor power cables are the only time I would do this; I would be curious if this might have eliminated the positioning motor and the spindle motor radiated noise.

 

kf2qd
User Rank
Platinum
Re: WHy not proper shielding?
kf2qd   8/15/2012 12:03:57 PM
NO RATINGS
Not knowing the particular construction of the motor you refer to - I would assume that the shield connection at the motor end is just continuing the shield connection through to parts on the motor not directly connected to electrical ground. This would keep the noise (pwm is really noisy..) from the motor cables from getting to the encoder/resolver wires in a parallel cable.

TJ McDermott
User Rank
Blogger
Re: WHy not proper shielding?
TJ McDermott   8/15/2012 12:06:17 PM
NO RATINGS
The shield is connected to motor frame.  Usually, motor frame and ground have continuity.

ttemple
User Rank
Platinum
Re: WHy not proper shielding?
ttemple   8/16/2012 4:46:32 PM
NO RATINGS
Cabe is busy making parts on his mill with his $12 solution, and everybody is arguing about how to properly shield something.

Why shield?  The machine is running, the solution was much cheaper than purchasing wire that may or may not actually solve the problem.  I have observed noise from spindle and servo drives that all the shielding, ferrite, and line reactors in the world was not able to solve.

Good job, Cabe.  I think your solution is excellent, and appropriate.

Jon Titus
User Rank
Blogger
Consider a current loop?
Jon Titus   8/14/2012 7:32:22 PM
NO RATINGS
Just wondered if you considered using a 4-20-mA current loop in place of the voltage signals.  Current loops are not susceptible to electrical noise that can scramble voltage signals. Avago Technologies has 8-pin DIP optically coupled 20-mA transmitters and receivers that simplify current-loop circuits and provide isolation, too.  Texas Instruments has at least one 20-mA transmitter.

I have driven a teletypewriter (circa 1978) with a 20-mA current loop over almost a quarter of a mile of wire.  Granted, at 110 baud.  But in short-distance wires, you can get a high data rate.

William K.
User Rank
Platinum
electrically noisy environments.
William K.   8/18/2012 9:05:50 PM
NO RATINGS
Shielding of signal leads is the way that I always start an installation. Also, in many instances, running an isolated ground connection for the sensor in the same cable as the sensor signal and power lines. While the standard practice for grounding shields is often the best choice, sometimes grounding the shield at a different point is the cure. My instructions have always been to carry the shield ungrounded until the signal conditioning input is reached, and if there is a problem I will ground it someplace else. That method avoids rework and allows the most flexability in grounding.

Note that these were custom designed and built production testing machines used in industrial factory enviroments. Sometimes the electrical noise could be read on an analog multimeter.

Tool_maker
User Rank
Platinum
What about the Mill
Tool_maker   8/21/2012 7:30:27 AM
NO RATINGS
I am most interested in to what kind of milling machine this kit is connected. What changes did you have to make to the mill? Is it still capable of manual operation? You gave the cost of a turnkey kit, but how did that compare to new CNC mill? Did you do this just for the satisfaction or was it to increase productivity? Does it have 3D capability?

Critic
User Rank
Platinum
Ad
Critic   9/21/2012 5:21:54 PM
NO RATINGS
Nice fix, but this reads too much like an advertisement/product endorsement.

Partner Zone
More Blogs from Sherlock Ohms
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Design News Webinar Series
9/10/2014 11:00 a.m. California / 2:00 p.m. New York
7/23/2014 11:00 a.m. California / 2:00 p.m. New York
7/17/2014 11:00 a.m. California / 2:00 p.m. New York
6/25/2014 11:00 a.m. California / 2:00 p.m. New York
Quick Poll
The Continuing Education Center offers engineers an entirely new way to get the education they need to formulate next-generation solutions.
Sep 22 - 26, MCU Software Development A Step-by-Step Guide (Using a Real Eval Board)
SEMESTERS: 1  |  2  |  3  |  4  |  5  |  6


Focus on Fundamentals consists of 45-minute on-line classes that cover a host of technologies. You learn without leaving the comfort of your desk. All classes are taught by subject-matter experts and all are archived. So if you can't attend live, attend at your convenience.
Next Class: September 30 - October 2
Sponsored by Altera
Learn More   |   Login   |   Archived Classes
Twitter Feed
Design News Twitter Feed
Like Us on Facebook

Sponsored Content

Technology Marketplace

Copyright © 2014 UBM Canon, A UBM company, All rights reserved. Privacy Policy | Terms of Service