GlennA
User Rank
Gold
alarm or fault memory
GlennA   6/4/2012 9:00:55 AM
NO RATINGS
Intermittent or momentary faults can be very hard to find.  On some machines, where possible, I added a latch to the alarm.  Other times, you just had to watch for the error.  One of the machines that I worked on had an air blow for spindle cleaning during tool change.  If the air pressure dropped below the switch setting the machine Emergency-Stopped on low air.  As soon as it stopped and shut off the air blow, the pressure built back up above the switch setting, and the error automatically reset .  Machine operators were notorious for not paying attention, so the complaint was usually "the machine just stopped".  Often the fix was just replacing the air supply hose with a shorter, larger diameter hose.

naperlou
User Rank
Blogger
Re: alarm or fault memory
naperlou   6/4/2012 9:34:17 AM
NO RATINGS
GlennA, I was working for a company that made simulators at one time.  I was involved in a R&D project to track errors and predict faults.  It was very interesting and an early application of AI in a real-time system.  We acutally logged every fault, even intermittent ones.  I learned about this working on satellites, actually.  Having an indicator that just blinked is not really useful, you need to keep that information.

TJ McDermott
User Rank
Blogger
Re: alarm or fault memory
TJ McDermott   6/4/2012 9:40:24 AM
NO RATINGS
Alarm history is vital when there is more than a handful of alarms to track.  On the other hand, having a hundred alarms to sort through can be just as difficult as the intermittent one.

GlennA
User Rank
Gold
Re: alarm or fault memory
GlennA   6/4/2012 9:46:44 AM
NO RATINGS
TJ McDermott;  Yes, too many alarm messages can also be a problem.  The ABB IRB 6400 S4c controller had several message lists, and a general list.  And some alarms would generate a secondary message, or even a tertiary message;  e.g. on a servo fault, each of the 6 axes would reply with a shutdown message.  It took some time to sort through the alarms to get to the primary error.

akili
User Rank
Iron
Re: alarm or fault memory
akili   6/4/2012 1:30:46 PM
NO RATINGS
You have to remember that this was around 1968 and control system design was moving from traditional relay technology to use of early (and expensive!) integrated circuits.  It just wasn't possible to latch every one of the hundreds of possible fault conditions and with hindsight, use of hard-wired printed circuit logic with IC's (mostly 7400 family in flat-packs) was smaller but no better than the relay version.  Only with the arrival of the microprocessor and true Programmable Logic Controller or PLC would all this be resolved sensibly.

tekochip
User Rank
Platinum
Surprised
tekochip   6/4/2012 5:14:41 PM
NO RATINGS
I'm surprised this wasn't discovered during testing of the lubrication system.  It's not intermittent, and there wasn't anything odd about 11:30, it's just that the lubrication system caused the machine to fail.  It makes me think that the lubrication system was tested outside of the machine, or when it was at idle.

Mydesign
User Rank
Platinum
Rocket science
Mydesign   6/5/2012 3:17:07 AM
NO RATINGS
1 saves
Rod, we had a similar experience while working with the rocket launch division. During the testing phase, when time counter is incremented from 23.59 to 00.00, the vernier engines stops fueling the booster rockets and hence there is change in thrust pressure. We had done all sort of testing to find out why this fuel injection missing happens at that particular time and finally found that a small bug in the Micro controller program. According to the program 00.00 is the resetting cycle, so whenever the clock reaches 00.00, it reads as a reset instruction.

Mydesign
User Rank
Platinum
Re: Surprised
Mydesign   6/5/2012 3:20:13 AM
NO RATINGS
1 saves
Tekochip, it seems that integration testing had not happened. By component wise all the devices or parts may work fine and by integration testing we can find how the system is behaving in a complex atmosphere or in collaborative mode.

akili
User Rank
Iron
Re: Surprised
akili   6/5/2012 10:51:28 AM
NO RATINGS
Now you have put your finger on the root of the problem!  The gearboxes and lubrication systems had been supplied and installed by a sub-contractor and the only "official" interface to our control system was the oil pressure signal.  The timeswitch didn't appear on any of our system diagrams and was fed from a spur from the antenna domestic mains, installed on an ad hoc basis by a sub-contract "sparks" at the request of the gearbox supplier.  That's how it got as far as it did - we were as surprised as anyone else when we found it.  Later earth-stations projects paid much more attention to such integration issues and consequently the commissioning threw up fewer and fewer surprises.  We still had some nasty experiences though, one in particular from an air-conditioning system.  But that's another story...

ChasChas
User Rank
Platinum
slow wear and tear and sneak-up problems
ChasChas   6/5/2012 12:12:10 PM
NO RATINGS
 

These kind of problems are the most challanging - especially since the equipment can't be shut down at will.

Page 1/2  >  >>
Partner Zone
More Blogs from Sherlock Ohms
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Sherlock Ohms highlights stories told by engineers who have used their deductive reasoning and technical prowess to troubleshoot and solve the most perplexing engineering mysteries.
Design News Webinar Series
9/10/2014 11:00 a.m. California / 2:00 p.m. New York
7/23/2014 11:00 a.m. California / 2:00 p.m. New York
7/17/2014 11:00 a.m. California / 2:00 p.m. New York
6/25/2014 11:00 a.m. California / 2:00 p.m. New York
Quick Poll
The Continuing Education Center offers engineers an entirely new way to get the education they need to formulate next-generation solutions.
Sep 22 - 26, MCU Software Development – A Step-by-Step Guide (Using a Real Eval Board)
SEMESTERS: 1  |  2  |  3  |  4  |  5  |  6


Focus on Fundamentals consists of 45-minute on-line classes that cover a host of technologies. You learn without leaving the comfort of your desk. All classes are taught by subject-matter experts and all are archived. So if you can't attend live, attend at your convenience.
Next Class: September 30 - October 2
Sponsored by Altera
Learn More   |   Login   |   Archived Classes
Twitter Feed
Design News Twitter Feed
Like Us on Facebook

Sponsored Content

Technology Marketplace

Copyright © 2014 UBM Canon, A UBM company, All rights reserved. Privacy Policy | Terms of Service